Goodman R-32 A2L Refrigerant Detection Sensor, SER2A08012S (8 ft Lead)
The SER2A08012S is the long-lead A2L refrigerant detection sensor Goodman specifies for its R-32 cased coils and its larger variable-speed air handlers. Manufactured by Sensata for Daikin North America and supplied with an 8-foot lead, it sits in the factory bracket inside the coil cabinet, samples the surrounding air for R-32 concentration, and reports to whatever control is running the mitigation logic — an A2L-equipped furnace board, a furnace integration kit, or a zoning control kit. The extra three feet of wire over the 5-foot SER2A05012S is the entire point: on a cased-coil installation the harness has to leave the coil and reach the furnace control board, which a 5-foot lead will not do.
Which R-32 Equipment Calls for the SER2A08012S?
Goodman stocks two A2L sensors and the only functional difference between them is lead length. Per the factory repair parts manuals, the SER2A08012S is the sensor listed for all eighteen CAPTA R-32 cased coil models and for the four largest AMVT R-32 variable-speed air handlers — the 3, 3.5, 4 and 5 ton AMVT36CP1300, AMVT42CP1300, AMVT48CP1300 and AMVT60DP1300.
Go the other direction and you need the short version. The 2 and 2.5 ton AMVT cabinets, every AMST R-32 air handler, and the Amana AWST R-32 air handlers all take the 5-foot SER2A05012S instead. Neither sensor substitutes for the other, and because the two part numbers differ by three characters and nothing visible on the housing, the safe habit is to read the sensor line item in the repair parts manual for your exact model rather than ordering off tonnage. For any other R-32 indoor model not named here, check that unit's parts manual before you order.
Ideal for: Technicians replacing a failed A2L sensor on a Goodman CAPTA R-32 cased coil or a 3 to 5 ton AMVT air handler, restoring a system that has locked into mitigation with a sensor fault, or replacing a sensor damaged while pulling and re-seating a coil during a compressor or TXV repair.
Matching an R-32 coil to a furnace that isn't A2L-equipped? The sensor needs somewhere to report. Add the Goodman Furnace Integration Kit 0230K00044 for a standard install, or the Goodman Zoning Integration Kit for R-32 Systems 0230K00007 where a zoning panel is in the mix, so the mitigation sequence can actually run.
Approved only for equipment listed for R-32. This sensor cannot be installed on an existing R-410A or R-22 coil, or on any system not approved for A2L refrigerant, and Goodman requires that it be replaced only with a sensor specified by the appliance manufacturer. Request part verification, contact Budget Heating, or call 813-885-7999.
What's Included
| Part | SER2A08012S — A2L Refrigerant Detection Sensor |
|---|---|
| OEM Brand | Goodman / Amana (Daikin North America) |
| Sensor Manufacturer | Sensata Technologies |
| Lead Length | 8 ft — the 5 ft version is SER2A05012S |
| Refrigerant Monitored | R-32 (A2L) |
| Specified For | Goodman CAPTA R-32 Cased Coils (All Models), Goodman AMVT36CP1300 / 42CP1300 / 48CP1300 / 60DP1300 |
| Reports To | A2L Furnace Control Board, Furnace Integration Kit, or A2L Zoning Control Kit |
| Mounting | Push-Pin Retained on the Factory Sensor Bracket |
| Not Approved For | R-410A, R-22, or Any System Not Listed for R-32 |
| Quantity | Sold Individually — One (1) Sensor |
This listing covers the sensor element by itself, not a kit. The bracket, push-pin retainers and control-board connector already in your coil or air handler are reused. What makes this part different from an ordinary sensor is what happens when it is missing or dead: the control does not simply post a code and carry on. It disconnects heating and cooling and holds the equipment in mitigation until a specified sensor is installed and communicating — which is why a coil that will not come out of mitigation is so often a sensor call rather than a refrigerant call.
Sensor Function & System Integration
SER2A08012S Sensor Construction & Detection
- Genuine OEM A2L refrigerant detection sensor, Goodman and Amana part number SER2A08012S
- Built by Sensata Technologies for Daikin North America, parent of the Goodman and Amana brands
- 8-foot lead sized to reach from a cased coil out to a furnace control board or integration kit
- Detects R-32 concentration in the air surrounding the indoor coil
- Seats in the factory sensor bracket and is retained by plastic push pins
- Keyed connector lands on the dedicated A2L sensor input — no splicing into thermostat wiring
- Polled by the control roughly once per second for continuous coverage
- Entirely passive in normal operation, with no impact on airflow, capacity or efficiency
- Engineered to last the service life of the coil it is installed in
- Direct one-for-one OEM replacement requiring no board changes or reprogramming
Furnace-Side Mitigation, Codes & Commissioning
- Drives the mitigation sequence on A2L-equipped Goodman and Amana furnace control boards
- On detection, gas heating is shut down and normal heating and cooling operation is disconnected
- Indoor blower is driven to maximum CFM to dilute and clear refrigerant from the cabinet and ductwork
- Optional ventilation and alarm outputs are energized during the alarm
- A2L furnace boards display an EAL error code while mitigation is active
- Blower runs an additional five minutes after the sensor clears before normal operation resumes
- Board diagnostics distinguish a sensor communication fault from an internal sensor fault
- Green board LED blinks to confirm active sensor communication and is off when no signal is present
- A2L monitoring is enabled by default and can be proof-tested through the board's verification menu, which simulates a leak
- Field wiring must be 18 AWG minimum with 1.58 mm insulation or otherwise protected from damage
Frequently Asked Questions
Why does this sensor have an 8-foot lead instead of 5 feet?
Because of where it has to reach. On a cased-coil system the sensor lives inside the coil but the control running the mitigation logic is in the furnace or in an integration kit mounted outside the coil, so the harness has to leave the coil cabinet and travel to that board. The larger AMVT cabinets need the same reach internally. Air handlers with the board close to the drain pan use the 5-foot SER2A05012S.
I'm putting a Goodman R-32 coil on an older gas furnace. Is the sensor all I need?
No. The sensor detects, but something has to act on the detection. An older furnace board has no A2L sensor input and no mitigation routine, so you also need a furnace integration kit, which gives the sensor a home and runs the required shutdown-and-purge sequence. If a zoning panel is part of the system, the A2L zoning control kit fills the same role. Wire the sensor before energizing either one.
My Goodman furnace is showing an EAL code. What does that mean?
EAL is the code an A2L-equipped Goodman furnace board displays while it is in leak mitigation mode. Gas heat is locked out and the blower is running at maximum CFM. It means the board is either seeing refrigerant or cannot get a valid reading from the sensor. Check for an actual leak first, then confirm the sensor is seated and plugged in, then read the board's flash pattern to see whether it is reporting a communication fault or a failed sensor.
Does replacing this sensor require recovering the refrigerant charge?
No. The sensor sits in the airstream inside the cabinet and is not part of the sealed refrigerant circuit, so a straightforward swap does not involve breaking into the system. It comes off the bracket on push pins and unplugs from the board. If you are on site because of an actual leak rather than a failed sensor, that repair is a separate job — and A2L refrigerant requires A2L-compatible recovery equipment and R-32 refrigerant to recharge.
Which AMVT air handlers take this sensor and which take the shorter one?
The split falls between 2.5 and 3 tons. AMVT36CP1300, AMVT42CP1300, AMVT48CP1300 and AMVT60DP1300 use the 8-foot SER2A08012S. The 2 ton AMVT24BP1300 and 2.5 ton AMVT30BP1300 use the 5-foot SER2A05012S. AMST and AWST air handlers use the 5-foot version across the entire lineup regardless of tonnage.
Can the A2L sensor function be disabled?
A2L-equipped Goodman furnace boards do include a menu setting that turns the A2L function off, intended for the case where an R-32-ready furnace is installed with R-410A equipment that has no A2L sensor. It is not a workaround for a faulty sensor on an R-32 system. Any system charged with R-32 is required to have a functioning refrigerant detection system, so on R-32 equipment the correct fix is replacing the sensor, not disabling the monitoring.