RACGYB180ADG000BACA0 | All-In-One | Horizontal or Downflow

15 Ton Rheem R454B 460V 3Ph Straight Air Package Unit, RACGYB180ADG000BACA0

· SKU 172905 · AHRI 215832192 · Package AC
Capacity
180,000 BTU
Refrigerant
R-454B
Average Rating:
List price: $21,735.00

Sale price:

$16,100.00
You save $5,635.00!
  • SKU: 172905
  • Availability:
    Usually Ships in 7 to 10 Business Days
  • Shipping:
    Calculated at Checkout
  • AHRI Certificate:
  • AHRI Number:
  • Product Type:
    Package AC
  • Tonnage:
    15
  • Operating Mode:
    Cool Only with Electric Heat
  • Refrigerant Type:
    R-454B
  • Airflow Direction:
    Downflow/Horizontal
  • Voltage:
    460V 3PH
  • 18kW Rheem RACG Commercial 460V 3Ph Heat Strip, RXJJ-G18KWD
  • 36kW Rheem RACG Commercial 460V 3Ph Heat Strip, RXJJ-G36KWD
  • 54kW Rheem RACG Commercial 460V 3Ph Heat Strip, RXJJ-G54KWD
  • 72kW Rheem RACG Commercial 460V 3Ph Heat Strip, RXJJ-G72KWD
Roof Curb
  • 15 - 25 Ton Rheem 14" Roofcurb, RXRX-DGC14
Curb Adapter
Economizer or Fresh Air Damper
  • 15 - 25 Ton Rheem Manual Fresh Air Damper, RXRF-AGA1
  • 15 - 25 Ton Rheem Motorized Fresh Air Damper, RXRF-AGB1
  • 15 - 25 Ton Rheem Downflow/Vertical Economizer, RXRD-11MGDAM3
  • 15 - 25 Ton Rheem Horizontal Economizer, RXRD-11MGHAM3
  • 15 - 25 Ton Rheem Hail Guard Outdoor Coil Louver Kit, RXRX-LKG01
Adding to cart… The item has been added

Rheem 15 Ton R-454B Commercial Packaged Air Conditioner — RACGYB180ADG000BACA0

The Rheem RACGYB180ADG000BACA0 is the 460V three-phase build of Rheem's 15-ton Commercial Renaissance Classic Series rooftop unit, producing 172,000 BTU/h AHRI net cooling at an 11.0 EER and 14.2 IEER on R-454B. Because it runs on 460V, each of its two scroll compressors draws about 11.9 A rather than 24.4 A on the 208/230V version, so large facilities can feed several rooftops from one 460V service with lighter feeders and breakers. It keeps the dual-circuit two-stage design, SmartShield interlaced MicroChannel coils, refrigerant leak detection, and standard belt-drive VFD supply fan in a convertible downflow or horizontal cabinet.

Is a 15-Ton Package Unit the Right Size?

This 15-ton unit opens Rheem's large-commercial RACG range and is matched to cooling loads near 172,000 to 180,000 BTU/h, which for many commercial buildings works out to roughly 6,000 to 9,000 sq ft of conditioned space. At this capacity, floor area is only a rough starting point — a full engineered load calculation is what actually sizes a rooftop this large.

Occupant density, outside-air ventilation, roof and wall insulation, glazing, and process or kitchen heat all move the requirement well above or below what the square footage suggests. The two-stage dual-circuit design and standard VFD supply fan let this unit modulate to first-stage cooling for much of the season, but that is not a substitute for a commercial (Manual N-style) load calculation, which confirms the capacity fits the zone and keeps humidity in check.

Ideal for: Large commercial and institutional zones in schools, campuses, warehouses, and industrial facilities that distribute power at 460V three-phase, where lighter branch wiring on big rooftops is an advantage.

Need more capacity? Step up to the 20-Ton Rheem R-454B 460V 3-Phase Package Unit (RACGYB240ADG000BACA0) for the largest single-zone commercial loads.

Recommended applications are general guidelines only. Actual capacity requirements depend on insulation, ventilation, occupancy, solar gain, ceiling height, and local design temperatures. Request free sizing assistance, contact Budget Heating, or call 813-885-7999.

What's Included

Model Number RACGYB180ADG000BACA0
Product Type Commercial Renaissance Classic Series Straight-Air (Cooling-Only) Packaged Air Conditioner
Nominal Capacity 15 Tons — 180,000 BTU/h (172,000 BTU/h AHRI net cooling)
Rated Efficiency 11.0 EER / 14.2 IEER
Refrigerant R-454B (A2L, factory charged — approx. 167/170 oz (dual circuit))
Compressors Two Scroll Compressors, Two Stages, Dual Refrigerant Circuits
Nominal Airflow 6,000 CFM — belt-drive supply fan with standard VFD, convertible downflow or horizontal
Electrical 460V, 3-Phase, 60 Hz
Minimum Circuit Ampacity 38 A
Max Overcurrent Protection 45 A
Manufacturer Warranty 5-Year Compressor / 1-Year Parts (Commercial)

The RACGYB180ADG000BACA0 ships as one factory-assembled, wired, and run-tested cabinet with both refrigerant circuits charged with R-454B, so there is no field line set to braze — set it, connect power and ducting, and commission. For curbed rooftop installs, pair it with the matching 15–25 Ton Rheem 14 in. roof curb (RXKG-CBH14). Browse more Rheem equipment or the full packaged air conditioner lineup for related sizes and voltages.

Unit Features

Cooling, Compressors & Coils

  • Two scroll compressors on independent refrigerant circuits providing two true stages of cooling
  • Factory-charged with low-GWP R-454B refrigerant and factory-installed refrigerant leak detection with automatic mitigation
  • Patented PlusOne SmartShield interlaced dual-circuit MicroChannel evaporator and condenser coils
  • TXV refrigerant metering with a solid-core liquid-line filter drier on each circuit
  • Rated 11.0 EER / 14.2 IEER at 180,000 BTU/h nominal (172,000 BTU/h AHRI net) cooling
  • High- and low-pressure protection with built-in Smart Logic and internal compressor line-break overload
  • Cooling operation to 125°F ambient; two-fan propeller condenser section
  • Heavy galvanized cabinet with forkable base rails and a flexible footprint (unit net weight approx. 1,951 lb)

Airflow, Controls & Serviceability

  • High-performance belt-drive supply fan delivering 6,000 nominal CFM
  • Standard Variable Frequency Drive (VFD) supply-fan control — runs at half speed on first-stage/constant-fan for lower energy use, quieter operation, and up to 126% more moisture removal at low load (meets ASHRAE 90.1-2022 and CA Title 24)
  • Field-convertible airflow — vertical downflow or horizontal side-flow
  • PlusOne ServiceSmart access: Qwik-Slide blower assembly and Qwik-Clean drain pan; slide-out rack holds eight 20 x 24 x 2 in. filters
  • PlusOne Diagnostics with dual 7-segment LED display, overflow condensate sensor, and external lockable gauge ports
  • Ships wired and run-tested; MERV 8 and MERV 13 filters available as factory or field options
  • 460V, 3-Phase, 60 Hz power: 38 A minimum circuit ampacity, 45 A maximum overcurrent protection, two compressors at 11.9 A RLA each
  • Field- and factory-installed options include economizers, low-ambient control, hot-gas reheat, hinged access, smoke detectors, and two-stage 18–72 kW electric heat kits

Specifications & Manuals

Product documentation includes RACG series technical specifications, installation instructions, and warranty information to assist with equipment selection, installation, and service. This unit carries a Rheem limited warranty; see the warranty document above for full coverage terms and conditions.

Frequently Asked Questions

What size space will the RACGYB180ADG000BACA0 cool?

It is matched to large commercial cooling loads near 180,000 BTU/h (172,000 BTU/h AHRI net), which often lands around roughly 6,000 to 9,000 sq ft of commercial space. Because occupancy, ventilation, glazing, and internal heat gain move the real load, size it with an engineered commercial load calculation rather than floor area alone.

Why choose the 460V RACGYB180ADG000BACA0 over the 208/230V model?

On 460V, 3-Phase, 60 Hz this unit draws far less current — a 38 A minimum circuit ampacity and 45 A maximum overcurrent protection (two compressors at 11.9 A RLA each) — versus the 208/230V build. That eases feeder and breaker sizing where a 460V service supplies several large rooftops. If your panel is 208/230V, order the 208/230V three-phase 15-ton version instead.

Is this a two-stage unit with two compressors?

Yes. Every RACGYB unit uses two scroll compressors on independent refrigerant circuits for two true stages of cooling, and a Variable Frequency Drive (VFD) supply fan is standard. Running at first stage with the VFD at reduced speed improves part-load efficiency (IEER) and moisture removal.

Does the VFD supply fan come standard?

Yes. A VFD on the belt-drive supply fan is standard on every RACGYB model. It ramps the fan up smoothly, runs at roughly half speed during first-stage and constant-fan operation for major energy savings and lower noise, and meets ASHRAE 90.1-2022 and California Title 24 multi-speed fan requirements.

Can this rooftop unit be installed downflow and horizontal?

Yes. Airflow is field-convertible between vertical downflow (for curbed rooftop openings) and horizontal side-flow, and the flexible footprint supports a variety of roof curbs. A matching 14 in. Rheem roof curb (RXKG-CBH14) is available for 15–25 ton RACG units.

Does this unit include heat, and what warranty applies?

This is a cooling-only (straight-air) unit; two-stage 18–72 kW electric heat kits are available as factory or field accessories. Rheem provides a limited warranty on the RACG series — typically a 5-year compressor and 1-year parts limited warranty for commercial applications. See the Rheem Limited Warranty document above for full terms.