Rheem 8.5 Ton R-454B Commercial Packaged Air Conditioner — RACDYB102ADG000AAAA0
The Rheem RACDYB102ADG000AAAA0 is the 460V three-phase version of Rheem's 8.5-ton Commercial Renaissance Classic Series rooftop package, producing 96,000 BTU/h AHRI net cooling at 11.2 EER and 14.8 IEER on R-454B. At 460V the compressor draws about 12.5 A rather than 26.8 A, an advantage where a 460V distribution panel supplies multiple large units. It retains the two-stage scroll compressor, all-microchannel coils, and belt-drive VFD blower moving 3,400 nominal CFM in a convertible downflow or horizontal cabinet.
Is a 8.5-Ton Package Unit the Right Size?
At 8.5 tons, this unit fills the gap between the common 7.5- and 10-ton sizes and targets loads around 96,000 to 99,000 BTU/h, often roughly 3,400 to 5,100 sq ft in typical commercial construction. Choosing an 8.5-ton rather than rounding to 10 tons can avoid an oversized system that short-cycles and struggles with humidity.
Ventilation rates, ceiling height, solar gain, lighting and plug loads, and local summer design temperature each shift the requirement. A high-occupancy dining room or fitness floor can fully load 8.5 tons where a lightly occupied warehouse office of the same area would be badly oversized. A proper commercial load calculation confirms whether this size — rather than the 7.5- or 10-ton — is the correct match.
Ideal for: Larger retail, assembly, and office zones within schools, campuses, and industrial buildings wired for 460V three-phase service.
Need more capacity? Step up to the 10-Ton Rheem R-454B 460V 3-Phase Package Unit (RACDYB120ADG000AAAA0) for larger zones that need more cooling capacity.
Recommended applications are general guidelines only. Actual capacity requirements depend on insulation, ventilation, occupancy, solar gain, ceiling height, and local design temperatures. Request free sizing assistance, contact Budget Heating, or call 813-885-7999.
What's Included
| Model Number | RACDYB102ADG000AAAA0 |
|---|---|
| Product Type | Commercial Renaissance Classic Series Straight-Air (Cooling-Only) Packaged Air Conditioner |
| Nominal Capacity | 8.5 Tons — 99,000 BTU/h (96,000 BTU/h AHRI net cooling) |
| Rated Efficiency | 11.2 EER / 14.8 IEER |
| Refrigerant | R-454B (A2L, factory charged — approx. 114 oz) |
| Compressor | Single two-stage scroll compressor |
| Nominal Airflow | 3,400 CFM — belt-drive blower with standard VFD, convertible downflow or horizontal |
| Electrical | 460V, 3-Phase, 60 Hz |
| Minimum Circuit Ampacity | 22 A |
| Max Overcurrent Protection | 30 A |
| Manufacturer Warranty | 5-Year Compressor / 1-Year Parts (Commercial) |
The RACDYB102ADG000AAAA0 ships as one factory-assembled, wired, and run-tested cabinet, so there is no field refrigerant line set to braze — it arrives charged with R-454B and ready to set, connect power and ducting, and commission. For curbed rooftop installs, pair it with the matching 7.5–12.5 Ton Rheem 14 in. roof curb (RXKG-DDD14). Browse more Rheem equipment or the full packaged air conditioner lineup for related sizes and voltages.
Unit Features
Cooling, Compressor & Coils
- Single two-stage scroll compressor factory-charged with low-GWP R-454B refrigerant
- Two stages of cooling for part-load operation, quieter running, and improved humidity control
- MicroChannel outdoor condenser and MicroChannel indoor evaporator coils for efficient heat transfer
- TXV refrigerant metering with a solid-core liquid-line filter drier
- Rated 11.2 EER / 14.8 IEER at 99,000 BTU/h nominal (96,000 BTU/h AHRI net) cooling
- High- and low-pressure protection with built-in Smart Logic and internal compressor overload
- Cooling operation to 125°F ambient; two condenser fans on a propeller condenser section
- 18-gauge galvanized cabinet with forkable base rails and an industry-standard footprint and connections
Airflow, Controls & Serviceability
- Belt-drive forward-curved centrifugal blower delivering 3,400 nominal CFM
- Standard variable frequency drive (VFD) blower control with variable-pitch pulleys and a quick-adjust belt system
- Convertible airflow — vertical downflow or horizontal side-flow
- PlusOne ServiceSmart access: Qwik-Change Flex-Fit filter rack, Qwik-Slide blower assembly, and Qwik-Clean composite drain pan
- PlusOne Diagnostics with dual 7-segment LED display and overflow condensate sensor
- External lockable gauge ports; ships wired and run-tested with four disposable filters (MERV 8 / MERV 13 available)
- 460V, 3-Phase, 60 Hz power: 22 A minimum circuit ampacity, 30 A maximum overcurrent protection, compressor RLA 12.5 A
- Field-installed accessories include economizers, hot-gas reheat/HumidiDry, roof curbs, hail guards, and smoke detectors
Specifications & Manuals
Product documentation includes RACD series technical specifications, installation instructions, and warranty information to assist with equipment selection, installation, and service. This unit carries a Rheem limited warranty; see the warranty document above for full coverage terms and conditions.
Frequently Asked Questions
What size space will the RACDYB102ADG000AAAA0 cool?
It is matched to commercial cooling loads near 99,000 BTU/h (96,000 BTU/h AHRI net), which often lands around roughly 3,400 to 5,100 sq ft of commercial space. Because occupancy, ventilation, glazing, and internal heat gain move the real load, size it with a commercial load calculation rather than floor area alone.
Why choose the 460V RACDYB102ADG000AAAA0 over the 208/230V model?
On 460V, 3-Phase, 60 Hz this unit draws far less current — a 22 A minimum circuit ampacity and 30 A maximum overcurrent protection (compressor RLA 12.5 A) — versus the 208/230V build. That eases wiring and breaker sizing where a 460V service feeds several rooftops. If your panel is 208/230V, order the 208/230V three-phase 8.5-ton version instead.
Is this a two-stage unit, and does it have a VFD?
Yes. Every RACDYB unit provides two stages of cooling, and a variable frequency drive (VFD) on the belt-drive blower is standard. The two-stage scroll compressor and VFD blower modulate to hold comfort and improve humidity control at part load.
Can this package unit be installed downflow and horizontal?
Yes. Airflow is field-convertible between vertical downflow (for curbed rooftop openings) and horizontal side-flow. A matching 14 in. Rheem roof curb (RXKG-DDD14) is available for 7.5–12.5 ton RACD units.
Does this unit include heat?
This is a cooling-only (straight-air) packaged air conditioner. Electric resistance heater kits are available as accessories on the RACD platform; if built-in heating is required, a gas/electric or heat-pump package unit is the better starting point.
Does the RACD package unit include a warranty?
Yes. Rheem provides a limited warranty on the RACD series — typically a 5-year compressor and 1-year parts limited warranty for commercial applications. See the Rheem Limited Warranty document above for full terms and conditions.
RACDYB 7.5-12.5 Ton Straight Cool Package Installation Manual
RACDYB 7.5-12.5 Ton Straight Cool Package Technical Specifications
Rheem Residential & Commercial Warranty