Product #180172: $6,740.00
  • Refrigerant Option:
  • Refrigerant Agreement:
  • Upload EPA 608 Certification:
  • 46627 / Kramer 2 HP R448A/R449A Medium-Temp Refrigeration Condensing Unit 208/230V 1PH, KFO200E4SDA (180135) -- 1
  • 46657 / Kramer Low Profile R448A/R449A Medium-Temp Refrigeration Evaporator 115V, KL6A141ADASC (180161) -- 1
6740
$6,740.00
Can't Decide? We can Help
Custom Quote
Have a large order? Need more customization?
Kramer Walk-In Cooler Refrigeration Systems

Kramer 2 HP R448A/R449A Medium-Temp Up to 18x18 Walk-In Cooler Refrigeration System KFO200E4SDA, KL6A141ADASC

· SKU 180172 · Commercial · Split System
Capacity
2 HP
Refrigerant
R-448A, R-449A
Temperature Range
Medium Temp
Average Rating:
List price: $8,760.00

Sale price:

$6,740.00
You save $2,020.00!
  • SKU: 180172
  • Availability:
    Usually Ships in 3 to 5 Business Days
  • Shipping:
    Calculated at Checkout
  • Product Type:
    Split System
  • Voltage:
    208-230V
  • Phase:
    Single Phase
  • Refrigerant Type:
    R-448A, R-449A
  • Manufacturer Warranty:
    1 Year
  • Factory Charge:
    Nitrogen
  • Horsepower:
    2 HP
  • Application:
    Walk-In Cooler
  • Temperature Range:
    Medium Temp
  • R-448A Opteon Refrigerant 25lb Jug
  • Opteon XP40- R-449A Refrigerant 25lb jug (Low GWP R22, R404A, R507, R407A/F Replacement)

Maximum file size is 524288KB, file types are bmp, gif, jpg, jpeg, jpe, jif, jfif, jfi, png, wbmp, xbm, tiff, txt, pdf, rtf, doc, docx, xls, xlsx, accdb, mdb, one, pps, ppsx, ppt, pptx, pub, odt, ods, odp, odg, odf

  • Kramer 2 HP R448A/R449A Medium-Temp Refrigeration Condensing Unit 208/230V 1PH, KFO200E4SDA
  • Kramer Low Profile R448A/R449A Medium-Temp Refrigeration Evaporator 115V, KL6A141ADASC
Adding to cart… The item has been added
Not sure on size? Get a free quote

Kramer 2 HP Medium Temperature Walk-In Cooler Refrigeration System

The Kramer KFO200E4SDA outdoor condensing unit and KL6A141ADASC low profile unit cooler form a factory-matched 2 HP medium temperature refrigeration package for walk-in coolers up to roughly 18 ft × 18 ft. A ZS15KAE scroll compressor drives a single three-fan KL6A141 coil, moving the line into full commercial-volume territory where a large sales-floor or back-of-house cooler runs hard all day. Configured for R448A or R449A refrigerant, it fits supermarkets, wholesale and distribution operations, large commissary kitchens, breweries, and beverage rooms.

Is a 2 HP Refrigeration System the Right Size?

This package is matched to medium temperature coolers up to about 18 ft × 18 ft holding 35°F to 38°F. At 25°F suction on R448A or R449A the KFO200E4SDA produces 16,840 BTUH at a 95°F ambient, and the matched system carries a rated capacity near 16,789 BTUH at 25°F SST, enough for roughly 320 square feet of well-insulated cooler at average usage.

Because floor plans vary, the system also covers long-and-narrow layouts that share a similar load, so a 12 ft × 22 ft galley cooler or an 8 ft × 32 ft reach-through runs on the same package as a square 18 ft × 18 ft room. It holds 14,790 BTUH at a 110°F ambient for hot rooftop and slab installations. High door traffic and warm product loaded in volume raise the load, so heavy-use rooms should size down one step; confirm against a calculated load.

Ideal for: supermarkets and grocery stores, wholesale and food distribution, large commissary and catering kitchens, craft breweries and taprooms, and beverage or dairy storage rooms.

Representative box sizes: this package is commonly applied to coolers such as 16 ft × 16 ft, 16 ft × 20 ft, 14 ft × 20 ft, and 18 ft × 18 ft, plus long-and-narrow layouts such as 12 ft × 22 ft, 10 ft × 28 ft, or 8 ft × 32 ft.

Need more capacity? Step up to the Kramer 2.5 HP KFO250E4SDA & KL6A161ADASC Refrigeration System. For a smaller room, see the Kramer 1.75 HP KFO180E4SDA & KL6A117ADASC system.

Recommended refrigeration applications are general guidelines only. Actual system requirements depend on insulation, ambient conditions, door openings, product load, and operating temperature. Request free sizing assistance, contact Budget Heating, or call 813-885-7999.

What's Included

Outdoor Condensing Unit KFO200E4SDA — 2 HP Medium Temperature Condensing Unit
Indoor Evaporator KL6A141ADASC Low Profile Unit Cooler
Application Medium Temperature Walk-In Cooler Refrigeration System
System Capacity Approximately 16,789 BTUH matched system (R448A/R449A, 25°F S.T., 10.3°F TD)
Refrigerant R448A or R449A
Compressor High-Efficiency Scroll Compressor
Evaporator Defrost Air Defrost
Electrical 208-230V, Single Phase, 60 Hz Condensing Unit
Evaporator Electrical 115V
Factory Charge Nitrogen Holding Charge — Refrigerant Field Supplied
Manufacturer Warranty 1 Year

The KFO200E4SDA condensing unit and the KL6A141ADASC low profile evaporator are also stocked individually for replacement work. Ordering them together as this matched package keeps the condensing unit and coil capacities aligned at design conditions. All units ship under a nitrogen holding charge, so plan on field-supplied R-448A or R-449A refrigerant and evacuation, charging, and commissioning by an EPA 608 certified technician.

Condensing Unit & Evaporator Features

KFO200E4SDA Outdoor Condensing Unit

  • 2 HP ZS15KAE scroll compressor for medium temperature commercial refrigeration
  • 16,840 BTUH at 95°F ambient and 25°F suction on R448A or R449A
  • 14,790 BTUH still available at 110°F ambient and 25°F suction for rooftop and unshaded slab installations
  • Integral liquid sub-cooling circuit providing an average 3°F to 5°F of sub-cooling for improved efficiency and stable expansion valve operation
  • Flooded head pressure control standard, supporting operation as outdoor ambient temperatures drop
  • Generously sized condenser coil with enhanced copper tubes and aluminum fins in an all-weather painted galvanized steel housing
  • Ships under a nitrogen holding charge, with a refrigerant receiver, isolation valve, and pressure relief plug
  • Liquid line with sealed filter and sight glass, factory crankcase heater, and electronic air defrost timer
  • Fixed high-pressure and adjustable low-pressure controls, with quick-access shut-off valves and color-coded point-to-point wiring
  • 208-230V single phase draw of 14.1 rated load amps and 68 locked rotor amps, on a 19.6 amp minimum circuit ampacity with 30 amp maximum overcurrent protection

KL6A141ADASC Low Profile Unit Cooler

  • 16,300 BTUH with R448A or R449A at 25°F SST and 10°F TD, and 14,100 BTUH on R404A
  • Multi-circuit coil fed by a refrigerant distributor for even refrigerant distribution across the coil face
  • Factory-mounted thermostatic expansion valve, selected for R448A and R449A service
  • Three balanced aluminum fans moving 2,355 CFM through a draw-through air pattern
  • Dual-speed electronically commutated 115V motors with thermal overload protection, compliant with California Title 24
  • 6 fins-per-inch coil using 3/8 in. enhanced copper tubes mechanically expanded into corrugated aluminum fins with die-formed collars
  • Air defrost configuration intended for coolers held at 35°F and warmer, factory wired to screw-type terminal strips
  • Embossed aluminum casing with baffled fan sections, NSF compliant and designed to mount flush to the ceiling
  • Removable 3/4-14 NPT drain fitting at the bottom of the pan, replaceable without changing the pan
  • 3/8 in. liquid and 5/8 in. suction connections, UL and cUL listed

Specifications & Manuals

Product documentation includes technical specifications, installation information, maintenance instructions, warranty information, and KL6 Series literature to assist with equipment selection, installation, and service. This system carries a 1 year manufacturer warranty; see the Kramer warranty documentation above for full coverage terms and conditions.

Frequently Asked Questions

What size cooler is the KFO200E4SDA sized for?

Medium-temperature coolers up to about 18 ft × 18 ft holding 35°F to 38°F, including long-and-narrow layouts of similar load. Confirm with a calculated heat load.

How is the KFO200E4SDA different from the 1.75 HP KFO180E4SDA?

It moves up to a ZS15KAE compressor producing about 16,840 BTUH at 95°F ambient and the three-fan KL6A141 coil, extending coverage to roughly 18 ft × 18 ft with stronger recovery in high-turnover rooms.

What line-set sizes does the KFO200E4SDA use?

The condensing unit and KL6A141 coil use a 3/8 in. liquid line and a 5/8 in. suction line. Final line sizing depends on the run length and lift between the units, which is set at installation.

What electrical service does the KFO200E4SDA require?

A dedicated 208-230V single-phase, 60 Hz circuit sized for about 14.1 rated load amps, with a 19.6 amp minimum circuit ampacity and 30 amp maximum overcurrent protection. The evaporator runs on 115V.

How high an outdoor ambient can it handle?

It is rated for outdoor installation and still delivers about 14,790 BTUH at a 110°F ambient, so it holds up on hot rooftops and unshaded slabs.

What operations is the KFO200E4SDA a good fit for?

Supermarkets, wholesale and food distribution, large commissary and catering kitchens, breweries, and beverage or dairy storage rooms.

 
 

 
 