6 Ton Rheem R454B 13.4 SEER2 460V 3Ph 125K BTU Gas Package Unit, RGECYB072ADT12BAAAA0

· SKU 172926 · AHRI 214803098 · Package AC
SEER2
13.4
Capacity
72,000 BTU
Refrigerant
R-454B

Understanding SEER2 Ratings: Learn how SEER2 is measured and the minimum efficiency your home needs »

Not Sure What Size System You Need? Sizing Calculator »

Average Rating:
List price: $10,294.00

Sale price:

$7,625.00
You save $2,669.00!
  • SKU: 172926
  • Availability:
    Usually Ships in 7 to 10 Business Days
  • Shipping:
    Calculated at Checkout
  • AHRI Certificate:
  • AHRI Number:
  • SEER2:
    13.4
  • Product Type:
    Package AC
  • Tonnage:
    6
  • Operating Mode:
    Gas
  • Refrigerant Type:
    R-454B
  • Airflow Direction:
    Downflow/Horizontal
  • Voltage:
    460V 3PH
Crating
  • Crating
Roof Curb
  • 3 - 6 Ton Rheem 14" Roof Curb ALL Models, RXKG-DCC14
Curb Adapter
Economizer or Fresh Air Damper
  • 3-6 Ton Rheem RGEC Manual Fresh Air Damper, RXRF-ACA1
  • 3-6 Ton Rheem RGEC Motorized Fresh Air Damper, RXRF-ACB1
  • 3-6 Ton Rheem RGECYB Downflow Economizer w/ Single Enthalpy, RXRD-01MCDBM3
  • Rheem LP Kit for RGEC Gas Package, RXGJ-FP40
Adding to cart… The item has been added

Rheem 6 Ton R-454B Gas/Electric Package Unit, 125,000 BTU/h Heat — RGECYB072ADT12BAAAA0

The Rheem RGECYB072ADT12BAAAA0 is a 6-ton Commercial Renaissance Classic Series packaged gas/electric unit that combines R-454B air conditioning with two-stage natural gas heat in one factory-assembled rooftop cabinet. Wired for 460V 3-phase power, it delivers 68,500 BTU/h AHRI net cooling at 11.0 EER / 14.6 IEER and pairs it with a 125,000 BTU/h nominal gas furnace (97,200 BTU/h heating output at 81% steady-state efficiency). A two-stage scroll compressor, all-microchannel coils, factory refrigerant leak detection, and a stainless-steel two-stage heat exchanger make this convertible downflow/horizontal unit a complete heating-and-cooling solution for light-commercial buildings that want cooling and high-capacity gas heat from a single 460V 3-phase rooftop.

Is a 6-Ton / 125,000 BTU Gas Package Unit the Right Size?

This unit matches 68,500 BTU/h of net cooling with a 125,000 BTU/h gas furnace, so it has to be sized for two loads at once. On the cooling side, 6 tons typically suits roughly 2,400 to 3,600 sq ft of light-commercial space; on the heating side, the 97,200 BTU/h output (high-capacity heat) should be matched to the building's design heating load and climate.

Cooling load depends on insulation, ventilation, occupancy, glazing, and local design temperatures, while heating load depends on climate, envelope, and ventilation air. The two-stage gas valve runs first stage at about 70% of full fire for quieter, more even heat and better part-load efficiency, with a high-fire temperature rise range of 40–70°F. Size both sides from a commercial load calculation rather than floor area alone so the unit neither short-cycles in cooling nor over- or under-heats the space.

Ideal for: High-occupancy retail, assembly, and large open commercial zones on 460V 3-phase power, in colder climates that need high-capacity gas heat.

Comparing options?

Recommended applications are general guidelines only. Actual cooling and heating requirements depend on insulation, ventilation, occupancy, solar gain, climate, and design temperatures. Request free sizing assistance, contact Budget Heating, or call 813-885-7999.

What's Included

Model Number RGECYB072ADT12BAAAA0
Product Type Commercial Renaissance Classic Series Packaged Gas/Electric Unit
Nominal Cooling 6 Tons — 68,500 BTU/h AHRI net cooling
Cooling Efficiency 11.0 EER / 14.6 IEER
Gas Heating 125,000 BTU/h nominal input — 97,200 BTU/h output (81% steady-state, two-stage)
Heat Exchanger Stainless steel, two-stage, direct spark ignition
Refrigerant R-454B (A2L, factory charged — approx. 85 oz)
Compressor Two-stage scroll compressor
Airflow Convertible downflow or horizontal
Electrical 460V, 3-Phase, 60 Hz
Minimum Circuit Ampacity 18 A
Max Overcurrent Protection 25 A
Manufacturer Warranty 5-Year Compressor / 10-Year Heat Exchanger / 1-Year Parts (Commercial)

The RGECYB072ADT12BAAAA0 ships as one factory-assembled, wired, and run-tested cabinet with R-454B charged and the gas furnace installed — set it, connect power, gas, and ducting, and commission. Add the Rheem RXRD-01MCDBM3 economizer for free cooling or the RXGJ-FP41 LP conversion kit for propane. Browse more Rheem equipment or the full packaged unit lineup for related sizes and configurations.

Unit Features

Cooling, Compressor & Coils

  • Two-stage scroll compressor factory-charged with low-GWP R-454B refrigerant
  • Two-stage cooling for part-load operation and improved humidity control
  • MicroChannel outdoor and indoor coils with TXV metering and a solid-core filter drier
  • Factory-installed A2L refrigerant leak detection with automatic mitigation
  • Rated 11.0 EER / 14.6 IEER at 68,500 BTU/h AHRI net cooling
  • High- and low-pressure protection with Smart Logic and internal compressor overload
  • Cooling operation to 125°F ambient; convertible downflow or horizontal airflow
  • Corrosion-resistant, gasket-protected cabinet with forkable base rails

Gas Heat, Controls & Serviceability

  • Two-stage natural gas heat — 125,000 BTU/h nominal input, 97,200 BTU/h output at 81% steady-state efficiency
  • Stainless-steel two-stage heat exchanger with direct spark ignition and first stage at ~70% of full fire
  • High-fire temperature rise range 40–70°F; field-convertible to LP with the Rheem LP conversion kit
  • Direct-drive constant-torque ECM indoor blower with multiple speed taps
  • CoreCommand control with PlusOne diagnostics and dual 7-segment LED display
  • Pre-wired for a field- or factory-installed economizer (free cooling)
  • 460V, 3-Phase, 60 Hz power: 18 A minimum circuit ampacity, 25 A maximum overcurrent protection
  • Ships wired and run-tested with a factory sub-base and gasketed duct openings

Specifications & Manuals

Product documentation includes RGEC series technical specifications, installation instructions, and warranty information to assist with equipment selection, installation, and service. This unit carries a Rheem limited warranty; see the warranty document above for full coverage terms.

Frequently Asked Questions

What cooling and heating capacity does the RGECYB072ADT12BAAAA0 provide?

It delivers 68,500 BTU/h AHRI net cooling (11.0 EER / 14.6 IEER) and 97,200 BTU/h of gas heating output from a 125,000 BTU/h nominal, two-stage furnace at 81% steady-state efficiency. Size both the cooling and heating sides from a commercial load calculation.

What power does the RGECYB072ADT12BAAAA0 require?

It is wired for 460V, 3-Phase, 60 Hz and needs a 18 A minimum circuit ampacity with a 25 A maximum overcurrent protection device. If your panel is 208/230V, order the 208/230V version instead.

Is the furnace two-stage, and can it run on propane?

Yes. The gas furnace is two-stage with a stainless-steel heat exchanger and direct spark ignition; first stage runs at about 70% of full fire for quieter, more even heat. It ships for natural gas and can be field-converted to LP (propane) with the Rheem RXGJ-FP41 LP conversion kit.

Can I add an economizer for free cooling?

Yes. This unit is pre-wired for an economizer. The matching Rheem RXRD-01MCDBM3 downflow economizer with single-enthalpy control brings in outdoor air for free cooling when conditions allow, and installs on 3–6 ton RGECYB units.

Can this unit be installed downflow and horizontal?

Yes. Airflow is field-convertible between vertical downflow (for curbed rooftop openings) and horizontal side-flow, so the same unit works on a curb or a slab with side duct connections.

How is the 6-ton gas package different from the smaller sizes?

Besides its higher 68,500 BTU/h AHRI net cooling, the 6-ton uses a two-stage scroll compressor (the 3–5 ton use single-stage) and is rated 11.0 EER / 14.6 IEER rather than in SEER2. It is offered only in the 125,000 BTU/h gas-heat configuration.