5/16" Liquid Line Protection for HVAC and Refrigeration Systems
The Sporlan C-0825-S Catch-All Liquid Line Filter Drier provides moisture, acid, and contaminant protection for air-conditioning and refrigeration systems requiring 5/16" ODF solder connections. Its 9 cubic inch molded desiccant core helps protect compressors, metering devices, and other refrigerant-system components from harmful contamination.
Designed for Moisture, Acid, and Contaminant Removal
The C-0825-S uses Sporlan’s molded porous Catch-All core to absorb and retain moisture and acids deep within the desiccant material. It also filters scale, solder particles, carbon, sludge, dirt, and other foreign matter while maintaining low refrigerant pressure drop.
Ideal for: Air-conditioning and refrigeration liquid lines requiring a compact filter drier with 5/16" ODF solder connections.
Connection note: The C-0825-S uses 5/16" ODF connections. Verify the line size carefully because the similar C-082-S and C-083-S use different connection sizes.
C-0825-S Filter Drier Features
- 5/16" ODF solder inlet and outlet connections
- 9 cu. in. molded porous desiccant core
- Removes moisture and acids from the refrigerant circuit
- Filters dirt, scale, solder particles, carbon, sludge, and other foreign matter
- Outlet safety filter provides additional contaminant protection
- Molded core helps prevent refrigerant from bypassing the desiccant
- Solid copper sweat connections
- Leak-resistant sealed shell construction
- Designed for low refrigerant pressure drop
- 650 PSI maximum working pressure
- UL listed
- Manufacturer part number 400433
Refrigerant Applications
The C-0825-S is designed for use with commercially available HCFC and HFC refrigerant and lubricant combinations when properly selected for the application.
Refrigerant compatibility and system capacity depend on the refrigerant, operating conditions, liquid temperature, and allowable pressure drop. Confirm proper filter drier selection before installation.
Installation
Install the C-0825-S in the refrigerant liquid line with the flow arrow pointing in the direction of refrigerant flow. The 5/16" copper connections are designed for standard HVAC brazing or sweat installation.
Protect the filter drier from excessive brazing heat and purge the tubing with nitrogen during installation. After brazing, pressure-test the system, repair any detected leaks, evacuate the refrigerant circuit, and charge the equipment according to the manufacturer’s instructions.
Filter drier selection, brazing, nitrogen purging, refrigerant handling, pressure testing, evacuation, and system charging should be completed by a qualified HVAC or refrigeration technician.
Frequently Asked Questions
What size connections does the Sporlan C-0825-S use?
The C-0825-S has 5/16" ODF solder connections on both the inlet and outlet.
Is C-0825-S the correct model number?
Yes. C-0825-S is a valid Sporlan model designed specifically with 5/16" ODF connections. It should not be confused with the C-082-S, which uses 1/4" connections.
How large is the C-0825-S filter drier?
The C-0825-S has a 9 cubic inch desiccant capacity, an overall length of approximately 5.31", and a body diameter of approximately 2.62".
What contaminants does the C-0825-S remove?
The Catch-All core helps remove moisture, acids, dirt, scale, solder particles, carbon, sludge, and other foreign material from the refrigerant circuit.
Is the C-0825-S a flare or solder filter drier?
The C-0825-S uses ODF solder or sweat connections and must be brazed into the refrigerant liquid line.
Which direction should the C-0825-S be installed?
Install the filter drier with refrigerant flowing in the direction indicated by the arrows printed on the shell.
| WEIGHT | 3 Pounds (Lb) |
|---|---|
| WIDTH | 3 Inches (In) |
| HEIGHT | 3 Inches (In) |
| COUNTRY OF ORIGIN | USA |
| UPC OR BARCODE | 68747223625 |
| HAZARDOUS MATERIAL | No |
| EPA CERT REQUIRED | No |
| LENGTH | 11 Inches (In) |
| BRAND | Sporlan |
| CONNECTION TYPE | ODF |
| SIZE | 1 1/8" |
| TYPE | Suction Line |